DP Level Transmitter Simulator

Explore hydrostatic level measurement in vented and pressurized tanks

UK SI

The tank

zero max ATM DP ↕

Liquid level
Transmitter elevation

Calibration points

% of rangeDP (inH₂O)Actual level (in)Output (mA)

“Actual level” is the tank level that produces that DP at the transmitter. In a calibration, you apply each pressure with a calibrator and compare the measured current with the expected one.

Indicated level1.647 m (error -0.004 m)
Transmitter output13.04 mA
4 mA 20 mA

The calculation

    Using the DP Level Transmitter Simulator

    Type: Tutorial
    Audience: Instrumentation students, technicians and process control engineers
    Goal: Explore how impulse-line arrangements, transmitter elevation and calibration range affect a 4–20 mA level signal.

    1. Select the installation

    Use the configuration tabs to compare:

    • Atmospheric vessel
    • Closed vessel with a dry leg
    • Closed vessel with a wet leg
    • Bubbler or purge tube
    • Remote seals with capillaries
    • Steam service with a condensation pot
    • Steam service with a pot and cooled high-pressure leg

    The diagram changes with the selected installation. The text below the diagram identifies the pressure relationship for the active configuration.

    2. Set the process conditions

    Adjust the liquid level and transmitter elevation with the sliders. Enter the vessel height, specific gravity, gas pressure and fill-fluid properties in the calculation panel. Select UK units for inches, inH₂O, psig and specific gravity, or SI units for metres, bar and density.

    For an initial exercise, use the default values and select each configuration in turn. Observe whether moving the transmitter changes the calculated differential pressure.

    3. Understand the calibration range

    The LRV is the differential pressure at 0% level and the URV is the differential pressure at 100% level. Enable automatic recalibration to make the simulator update the range when the installation parameters change. Disable it to model a real transmitter whose range remains fixed until a technician recalibrates it.

    Use Recalibrate range now after changing the installation or density. The calibration table then shows the expected pressure and output current at 0%, 25%, 50%, 75% and 100% of range.

    4. Investigate elevation errors

    With automatic recalibration disabled, move the transmitter above and below the tank zero level. Compare the indicated level with the actual level and watch the error message. In a real installation, this error is corrected by setting the LRV and URV for the installed elevation, not by changing the process level.

    Elevation is intentionally locked for bubbler, remote-seal and condensation-pot configurations where the model shows that the transmitter elevation cancels. The cooled high-pressure leg steam configuration remains sensitive to the difference between reference and process-leg fluid densities.

    5. Interpret the output

    The simulator converts the measured differential pressure into current using:

    $$ \mathrm{mA} = 4 + 16 \frac{\mathrm{DP} - \mathrm{LRV}}{\mathrm{URV} - \mathrm{LRV}} $$

    Values outside the configured range are highlighted as under-range or over-range conditions. The calculation steps show the high-pressure side, low-pressure side, differential pressure, range conversion and level error.

    DP Level Measurement Fundamentals

    A differential-pressure transmitter measures liquid level indirectly from hydrostatic head. The high-pressure (HP) connection senses the process pressure at the lower tap and the low-pressure (LP) connection provides the reference pressure. The transmitter output is proportional to the calibrated differential pressure, not directly to level.

    Atmospheric vessel

    The LP side vents to atmosphere and the HP side is connected at the zero level:

    $$ \mathrm{DP} = \mathrm{SG}(h-e) $$

    Here, h is liquid height and e is transmitter elevation relative to zero. A transmitter below zero therefore produces a positive zero-level DP (zero suppression).

    Closed vessel with a dry leg

    The gas pressure acts on both sides and cancels:

    $$ \mathrm{DP} = [P_g + \mathrm{SG}(h-e)]-P_g = \mathrm{SG}(h-e) $$

    The reference line must remain free of condensate. Liquid accumulation in a dry leg creates an additional head and causes a measurement error.

    Closed vessel with a wet leg

    The LP line is filled with a reference fluid up to the upper tap:

    $$ \mathrm{DP} = \mathrm{SG}(h-e)-\mathrm{SG}_{\mathrm{fill}}(H_m-e) $$

    The zero-level DP is normally negative, so the transmitter requires a negative LRV. The fill fluid must remain compatible with the process and stable over the operating temperature range.

    Bubbler or purge tube

    A low flow of air or nitrogen exits from a dip tube at the zero level. The back pressure is approximately the liquid head:

    $$ P = \mathrm{SG}\,h $$

    The gas column has negligible weight, so transmitter elevation does not affect the reading. The purge pressure must exceed the maximum liquid head and the purge flow must remain low enough to avoid friction error.

    Remote seals and capillaries

    Two diaphragm seals transfer pressure through capillaries containing the same fill fluid:

    $$ \mathrm{HP} = P_g + \mathrm{SG}\,h - \mathrm{SG}_{\mathrm{fill}} e $$

    $$ \mathrm{LP} = P_g + \mathrm{SG}_{\mathrm{fill}}(H_m-e) $$

    $$ \mathrm{DP} = \mathrm{SG}\,h - \mathrm{SG}_{\mathrm{fill}} H_m $$

    The transmitter elevation cancels. Unequal capillary temperatures, different fill-fluid densities and diaphragm stiffness are important sources of error.

    Steam service

    For a steam vessel with a condensation pot, the reference leg remains filled with condensate. The simplified model is:

    $$ \mathrm{DP} = h(\mathrm{SG}-\mathrm{SG}_{\mathrm{steam}})-H_m(\mathrm{SG}_{\mathrm{ref}}-\mathrm{SG}_{\mathrm{steam}}) $$

    The range depends on the process liquid, steam and condensate densities. A configuration with a cooled HP leg uses the cooled process-leg density separately, so the installed elevation can matter when the two leg densities differ.

    4–20 mA conversion

    For a linear transmitter:

    $$ \mathrm{mA} = 4 + 16 \frac{\mathrm{DP} - \mathrm{LRV}}{\mathrm{URV} - \mathrm{LRV}} $$

    The LRV and URV must be calculated for the actual impulse-line arrangement and installed elevation. A correct process calculation can still produce a wrong level indication when a transmitter is ranged for a different installation.

    Model limitations

    The model uses hydrostatic heads and idealized reference-leg conditions. Use the results to explore calibration and installation effects.

    Frequently Asked Questions

    Why is the LRV negative for a wet leg or remote-seal installation?

    The reference leg or capillary fill fluid creates a constant pressure on the LP side. At zero process level, the HP side is lower than the LP side, so the transmitter must be ranged with a negative LRV.

    Why does moving the transmitter not change the reading in the bubbler configuration?

    The pressure is generated at the open end of the purge tube. The gas column has negligible density compared with the liquid, so the transmitter elevation does not add a meaningful hydrostatic head.

    What happens when a dry leg fills with condensate?

    The condensate adds pressure to the LP side. The transmitter then interprets the reference-leg head as a change in level, producing a systematic level error. Drainage, heat tracing or a wet-leg design may be required depending on the service.

    Why does gas pressure not affect the level reading in a closed vessel?

    In a correctly configured dry- or wet-leg installation, the vessel gas pressure is transmitted to both sides and cancels from the differential pressure. The reference liquid head still remains in a wet leg.

    Why does the cooled HP-leg steam case depend on transmitter elevation?

    The model contains different fluid densities in the reference and HP legs. Moving the transmitter changes the lengths of those columns, and their unequal hydrostatic heads do not cancel.

    What do LRV and URV mean?

    LRV is the input differential pressure corresponding to 0% output, normally 4 mA. URV is the input differential pressure corresponding to 100% output, normally 20 mA. Both are pressure values, not level values.

    Why does the simulator show an indicated level different from the actual level?

    Automatic recalibration may be disabled while the transmitter elevation, density or impulse-line arrangement has changed. The transmitter is retaining its old range, which is the same error mechanism found in an incorrectly ranged plant instrument.